ELECTRONIC HYGROSTAT |
|
|
|
EFR012 |
Features |
|
High switching capacity |
Adjustable humidity |
Change-over contact |
DIN rail mounted |
|
When the relative humidity in the power distribution box exceeds 65%, EFRO12 will control the heater heating, in order |
to reduce the moisture condensation and effectively prevent corrosion. Compared with mechanical thermostat, EFRO12 |
with low hysteresis, making it's switching point and setting accuracy more precise. |
|
|
|
|
|
|
|
|
Technical Data |
|
Switch temperature difference: |
|
5% RH(±3% RH tolerance) at 25℃ |
|
|
|
Sensor element: |
|
PTC |
|
|
|
Contact type: |
|
Change-over |
|
Contact resistance: |
|
< 10m Ω |
|
|
|
Service life: |
|
>100,000 cycles. |
|
Max. switching capacity: |
|
28VDC,16A |
|
EMC: |
|
Acc. To EN 55014-1-2, EN 61000-3-2, EN 61000-3-3 |
|
|
|
Connection: |
|
5-pole terminal, damping torque0.5Nm max.:rigid wire2.5mm²stranded wire (with wire end ferrule) 1.5mm² |
|
|
Mounting: |
|
Clip for 35mm DIN rail,EN60715 or for exit filter EF 118 Series |
|
Dimensions: |
|
64.5×42×38mm |
|
Weight: |
|
Approx.80g |
|
Installation position: |
|
Variable |
|
Operating/Storage temperature: |
|
0 to+60℃(32 to+140°F)/-45 to +80℃ (-49 to+176°F) |
|
Protection type: |
|
IP20 |
|
|
Example of connection |
|
Art. No. |
Operating voltag |
Setting range humidity |
01245.0-00 |
230VAC,50/60Hz |
40 to 90% RH VDE+UL intended |
01246.0-00 |
230VAC,50/60Hz |
65% RH pre-set VDE+UL intended |
01245.9-00 |
120VAC,50/60Hz |
40 to 90% RH UL intended |
01246.9-00 |
120VAC,50/60Hz |
65% RH pre-set UL intended |
|
|
|